SPEC 83251

NS75 CSA Quadruplex LLDPE/PVC Service Drop. ACSR Neutral - Messenger

Aluminum Conductors With Linear Low Density Polyethylene And Polyvinyl Chloride Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compact 1350-H19 aluminum
  2. Messenger:ACSR Neutral
  3. Insulation:Linear Low Density Polyethylene (LLDPE) and Polyvinyl Chloride (PVC)

Applications and Features:

Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures 75°C for Linear Low Density Polyethylene (LLDPE) and Polyvinyl Chloride (PVC) insulated conductors.

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • CSA 22.2 No. 129 Neutral Supported Cable
  • Table 1 – Weights and Measurements
    Stock NumberPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/Kcmilinchlb/1000ft
    6632043/070.4231050.6333/01.528972
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    Table 2 – Electrical and Engineering Data
    Phase Cond. SizeDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 75°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    3/00.10540.14440.0320.0139192
    Notes:
    1. DC resistances include a 1% length factor for plexing.
    2. Inductive reactance assumes the neutral is carrying current.
    3. Phase conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the phase conductor only.
    6. Ampacity based on conductor temperature of 75°; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

    Neutral Code Word

    SizeCode WordOD (inches)
    #6Bass0.182
    #2Carp0.290
    2/0Hake0.410
    3/0Cusk0.461
    4/0Scup0.517

    Revision: 1.000.001

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC