SPEC 83001

Single 600 Volt USE-2 Aluminum Underground Service Entrance

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE) Type USE-2

For information about our Cable-Rejuvenation Services please visit us at:  Cable-Rejuvenation Services
You can email us at: Cable-Rejuvenation Services

Applications and Features:

Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene UL listed as Type USE-2 . These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • UL 854 Service Entrance Cable
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchlb/1000ft
    105536Duke600610.8651101.086704
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    ! Conductor is ASTM B901
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeMin Bending RadiusNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    Duke6005.436000.0290.0370.039385385
    Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC