SPEC 51010

Flexible Hook-Up Wire/Appliance Wire Styles 1007/1569

80°C or 105°C Dry. 300 Volts. Flexible Stranded Copper Conductor. PVC Insulation.

...

Construction:

  1. Conductor:Class K, stranded bare copper or tinned copper per ASTM B3 or B8 and B174
  2. Insulation:Polyvinyl Chloride (PVC). All colors available; Stripes available upon request

Applications and Features:

For us in internal wiring of appliances or electronic equipment where not subject to movement or mechanical damage.

  • AWM Style 1007: 80°C Dry, 300V
  • AWM Style 1569: 105°C Dry, 300V
  • TR-64: 90°C Dry
  • AWM I A/B: 105°C Dry, 300V

  • Rated for VW-1 and FT1

    Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material
  • CSA C22.2 No. 127 Equipment and Lead Wires
  • CSA C22.2 No. 210 Appliance Wiring Material Products
  • Sample Print Legend:

    XX AWG (XX{mm2}) E57498 {RU} AWM 1569 105C OR 1007 80C 300V VW-1 -- 156205 {CSA} TR-64 90°C FT1 OR AWM I A/B 105C 300V FT1
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. StrandsCond. MetalDiameter Over Cond.Insul. ThicknessApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°C
    AWGstrandsinchmilinchlb/1000ftΩ/1000ftΩ/1000ft
    AWM
    F24002247TCu0.022150.057226.10026.883
    F24008247Cu0.022150.057226.10026.883
    F22021227TCu0.028150.062316.40016.520
    F22016227Cu0.028150.062316.40016.520
    F200302010TCu0.037150.067411.31913.638
    F200272010Cu0.037150.067411.31913.638
    F180411816TCu0.044150.07967.1488.613
    F180351816Cu0.044150.07977.1488.613
    F160251626TCu0.059150.091104.4875.406
    F160931626Cu0.059150.091104.4875.406
    F140281441TCu0.073150.110152.8143.391
    F141881441Cu0.073150.110152.8143.391
    F120351265TCu0.094150.123231.7742.137
    F121291265Cu0.094150.123231.7742.137
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 1.000.030

    Updated On: March 1, 2024, 5:10 p.m. UTC

    Ampacity
    QR Code