SPEC 44070

Machine Flexible Hookup

105ºC Dry. 60/75ºC Moisture Resistant. 600/1000 Volts. Flexible Stranded Tinned Copper Conductor. PVC lnsulation .

...

Construction:

  1. Conductor:Flexible stranded tinned copper per ASTM B33
  2. Insulation:Polyvinyl Chloride (PVC)
  • Colors: Other Colors available; including Green with 2x15% +/- 5% Tolerance Yellow Extruded Stripe. Other stripes available.
  • Extruded stripes limited to sizes 4/0 AWG and smaller. 250Kcmil available in solid colors only.
  • Applications and Features:

    Southwire’s Machine Flexible Power cables are suited for use in wet and dry areas, conduits, ducts, troughs, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. 1/0 AWG & Larger rated for CT USE

    Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 83 Thermoplastic Insulated Wires and Cables Type THHN
  • UL 758 Standard for Appliance Wiring Material Style 20886
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • Sample Print Legend:

  • SOUTHWIRE 18 AWG (0.823mm2) E51583 (PLANT ID CODE) (UL) MTW OR AWM 1011/1015/1230/1335/1345 600V OR 1032 1000V MOISTURE RESISTANT VW-1 -- 156205 CSA TEW 105°C 600V FT1 OR AWM I A/B 105°C 600V FT1 -- CE RoHS-2 MADE IN USA
  • SOUTHWIRE® 8 AWG (8.37mm2) E69567 (PLANT ID CODE) (UL) BC-5W2 OR MTW OR THHW OR AWM 1011/1028/1231/ 1337 600V OR 1032 1000V MOISTURE RESISTANT OIL RES I SUN RES VW-1 -- 156205 CSA TEW 105°C 600V FT1 OR AWM I A/B 105°C 600V FT1-CE RoHS-2 MADE IN USA
  • SOUTHWIRE® 250 MCM (127mm2) E51583 (PLANT ID CODE) (UL) MTW OR THHW FOR CT USE OR AWM 1284/1339 600V OR 10269 1000V. OIL RES 1 SUN RES VW-1 - 156205 CSA AWM A/B 105°C 600 V - CE RoHS-2 MADE IN USA
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsDiameter Over ConductorInsul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ft
    F1872118.016.00.04630.00.1069.3
    F1650216.026.00.05730.00.11712.9
    F1464714.041.00.07230.00.13218.4
    F1227612.065.00.09130.00.15126.9
    F1023710.0105.00.11530.00.17540.6
    F081778133.00.16245.00.25272.0
    F061896133.00.20460.00.324113.0
    F041274133.00.26760.00.387166.0
    F021332133.00.35260.00.472259.0
    F010761259.00.36180.00.521324.0
    F150971/0259.00.40180.00.561401.0
    F251002/0259.00.580.00.66495.0
    F351033/0259.00.50680.00.666601.0
    F451054/0259.00.5880.00.74773.0
    F25010250259.00.64595.00.835934.0

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC ResistanceAC Resistance @ 90°CAllowable Ampacity In Conduit At 60°CAllowable Ampacity In Conduit At 75°CAllowable Ampacity In Conduit At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftAmpAmpAmp
    F1872118.00.4213.07.078.847.07.07.0
    F1650216.00.4721.04.185.22610.010.010.0
    F1464714.00.5333.02.633.28815.015.015.0
    F1227612.00.652.01.662.07520.020.020.0
    F1023710.00.783.01.041.330.030.030.0
    F0817780.911320.6520.815405055
    F0618961.042100.4110.514556575
    F0412741.333340.2580.323708595
    F0213321.655310.1620.20395115130
    F0107611.826700.1290.161110130145
    F150971/02.068450.1020.128125150170
    F251002/02.1810650.0810.102145175195
    F351033/02.4213420.0640.081165200225
    F451054/02.6616930.0510.064195230260
    F250102502.9620000.0430.055215255290