SPEC 26661
HVTECK AL 3/C 345NLEPR TS PVC AIA PVC 35kV 100% CSA
3 Conductor, 345 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:345 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 345 NLEPR AIA 35kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 1/0 | 19 | 0.336 | 1.063 | 345 | 1.123 | 6 | 2.701 | 3.031 | 75 | 3.181 | 3958 |
TBA | 2/0 | 19 | 0.376 | 1.103 | 345 | 1.163 | 6 | 2.787 | 3.117 | 75 | 3.267 | 4193 |
TBA | 3/0 | 19 | 0.423 | 1.150 | 345 | 1.210 | 6 | 2.939 | 3.269 | 85 | 3.439 | 4697 |
TBA | 4/0 | 19 | 0.475 | 1.202 | 345 | 1.262 | 6 | 3.051 | 3.381 | 85 | 3.551 | 5036 |
TBA | 250 | 37 | 0.520 | 1.256 | 345 | 1.316 | 4 | 3.168 | 3.498 | 85 | 3.668 | 5429 |
TBA | 350 | 37 | 0.616 | 1.352 | 345 | 1.412 | 4 | 3.375 | 3.705 | 85 | 3.875 | 6119 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1/0 | 22.3 | 1901 | 0.168 | 0.211 | 0.062 | 0.050 | 0.566+j0.316 | 0.211+j0.050 | 4.7 | 181 | 200 |
2/0 | 22.9 | 2396 | 0.133 | 0.167 | 0.058 | 0.048 | 0.518+j0.303 | 0.167+j0.048 | 5.9 | 208 | 228 |
3/0 | 24.1 | 3020 | 0.105 | 0.132 | 0.054 | 0.046 | 0.479+j0.289 | 0.132+j0.046 | 7.4 | 239 | 258 |
4/0 | 24.9 | 3809 | 0.0836 | 0.105 | 0.050 | 0.045 | 0.447+j0.274 | 0.105+j0.044 | 9.4 | 273 | 292 |
250 | 25.7 | 4500 | 0.0707 | 0.089 | 0.048 | 0.043 | 0.425+j0.261 | 0.089+j0.043 | 11.1 | 302 | 321 |
350 | 27.1 | 6300 | 0.0505 | 0.064 | 0.042 | 0.041 | 0.391+j0.238 | 0.065+j0.041 | 15.5 | 368 | 385 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
TBA | 1/0 | 19 | 8.53 | 27.00 | 8.76 | 28.52 | 6 | 68.61 | 76.99 | 1.91 | 80.80 | 5890 |
TBA | 2/0 | 19 | 9.55 | 28.02 | 8.76 | 29.54 | 6 | 70.79 | 79.17 | 1.91 | 82.98 | 6240 |
TBA | 3/0 | 19 | 10.74 | 29.21 | 8.76 | 30.73 | 6 | 74.65 | 83.03 | 2.16 | 87.35 | 6990 |
TBA | 4/0 | 19 | 12.07 | 30.53 | 8.76 | 32.05 | 6 | 77.50 | 85.88 | 2.16 | 90.20 | 7494 |
TBA | 250 | 37 | 13.21 | 31.90 | 8.76 | 33.43 | 4 | 80.47 | 88.85 | 2.16 | 93.17 | 8079 |
TBA | 350 | 37 | 15.65 | 34.34 | 8.76 | 35.86 | 4 | 85.73 | 94.11 | 2.16 | 98.43 | 9106 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1/0 | 566.42 | 8459 | 0.5512 | 0.69 | 0.0189 | 0.1640 | 0.566+j0.316 | 0.211+j0.050 | 4.7 | 181 | 200 |
2/0 | 581.66 | 10662 | 0.4364 | 0.55 | 0.0177 | 0.1575 | 0.518+j0.303 | 0.167+j0.048 | 5.9 | 208 | 228 |
3/0 | 612.14 | 13439 | 0.3445 | 0.43 | 0.0165 | 0.1509 | 0.479+j0.289 | 0.132+j0.046 | 7.4 | 239 | 258 |
4/0 | 632.46 | 16950 | 0.2743 | 0.34 | 0.0152 | 0.1476 | 0.447+j0.274 | 0.105+j0.044 | 9.4 | 273 | 292 |
250 | 652.78 | 20025 | 0.2320 | 0.29 | 0.0146 | 0.1411 | 0.425+j0.261 | 0.089+j0.043 | 11.1 | 302 | 321 |
350 | 688.34 | 28035 | 0.1657 | 0.21 | 0.0128 | 0.1345 | 0.391+j0.238 | 0.065+j0.041 | 15.5 | 368 | 385 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C